Description of Peripheral Electrical Devices

- Jan 21, 2019 -

PartMounting LocationFunction Description
MCCB  

(moulded case 

circuit breaker)

Power receiving side 

Interrupt the power supply 

when overcurrent occurs on 

downstream devices

         
Contactor Between MCCB 
and AC drive input side  
Start and stop the AC drive.

Do not start and stop the 

AC drive frequently by switching

the contactor on and off 

(less than twice per minute) 

nor use it to directly start 

the AC drive.

AC input reactor    AC drive input side

Reduce the external conduction 

and radiation interference of 

the AC drive.

• Decrease the conduction 

interference flowing from 

the power end to the AC drive 

and improve the anti-interference

capacity of the AC drive.

DC reactor      MD series AC drive
of 7.5G and above 
configured with DC 
reactor as standard

 • Improve the power factor of the

input side.

• Improve the efficiency and thermal 

stability of the AC drive.

 • Eliminate the impact of higher 

harmonics the AC drive input side 

and reduce the external conduction 

and radiation interference.

AC output reactorBetween AC drive  
output side and the 
motor, close to the AC drive, 

The output side of the AC drive generally has much higher harmonics. 

When the motor is far from the AC motor, close to the AC drive,there is much distributed capacitance in the circuit and certain harmonics may cause resonance in the circuit, bringing about

the following two impacts:

• Degrade the motor insulation performance and damage the motor in the long 

run.

• Generate large leakage current and 

cause frequent

AC drive protection trips.

If the distance between the AC drive 

and the motor

is greater than 100 m, install an AC 

output reactor.

1) Do not install the capacitor or surge suppressor on the output side of the AC drive.

Otherwise, it may cause faults to the AC drive or damage to the capacitor and surge 

suppressor.

2) Inputs/Outputs (main circuit) of the AC drive contain harmonics, which may interfere 

with the communication device connected to the AC drive. Therefore, install an 

anti-interference filter to minimize the interference.

3For more details on peripheral devices, refer to related selection manual.